Φ12x6.9mm - H2R12-600xx

Φ12x6.9mm - H2R12-600xx

AC Power line N-PE applications

Class I and Class II Surge protection

Voltage : 600V

Up: <1100V

Uc:  255V

In:  20KA 

Iimp: 8KA

Imax: 40KA


Specification of  H2R12-600xx

Dc spark-over voltage (100V/s)      1)

600V ±20%

Maximum impulse spark-over voltage (1K-V/μs)

1100V

Breakdown time   

           - typical values

100ns

20ns

Insulation resistance @DC250V

  1000MΩ

Class I  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μ                              In

Impulse current 10/350μ                                            Iimp

 

255V

20KA

8KA

Class II  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μ                              In

Maximum discharge current 8/20μ                            Imax

 

255V

20KA

40KA

capacitance at 1MHz

3pF

Weight

4g

UL 1449 Certification

On the UL List


 ul.png

Delivery time

20days

Operation and storage temperature

-40 … +90

Marking, Blue

1) At delivery AQL 0.65 level II Military Standard 105E.

2)In ionized mode

Test according to ITU-T Rec. K.12

2R 600 YY

600 - Nominal voltage

YY - Year of production