Φ16x4.5mm - H2R16-800x

AC Power line N-PE applications

Class I and Class II Surge protection

Voltage : 800V

Up: 1500V

Uc:  264V

In:  20KA 

Iimp: 8KA

Imax: 40KA

If:  100A

TOV: 300A


Specification of  H2R16-800x

Dc spark-over voltage (100V/s)      1)

600V-1000V

Front of wave spark-over voltage at 1.2/50us, 6KV

1500V

Breakdown time   

           - typical values

100ns

20ns

Insulation resistance @DC250V

  1000MΩ

Class I  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μs                               In

Impulse current 10/350μs                                             Iimp

Follow Current at 50/60Hz at 264V                               If

 

264V

20KA

8KA

100A

Class II  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μs                               In

Maximum discharge current 8/20μs                            Imax

Follow Current at 50/60Hz at 264V                              If

 

264V

20KA

40KA

100A

AC discharge current (TOV at 1200V ,1 operation 50Hz,0.2 s)

300A

capacitance at 1MHz

6pF

Weight

~ 4g

UL 1449 Certification

On the UL List


 ul.png

Delivery time

20days

Operation and storage temperature

-40 … +90

Marking, Blue

1) At delivery AQL 0.65 level II Military Standard 105E.

    Approvals/ Standards   IEC61643-11

2R800 YY

800 - Nominal voltage

YY - Year of production