Tel:+86-755-27465585
Fax:+86-755-27270662
Email:   sales@huaandz.com
Website:   www.huaandz.com
Add:5F,Building C,No.30,Aviation Road,SanWei,XiXiang Street,BaoAn District,ShenZhen,China


Your Current Location > Home > Products > Gas Discharge Tubes

Φ20x4.2mm - H2R20-600

AC Power line N-PE applications

Class I and Class II Surge protection

Voltage : 600V

Up: 1500V

Uc:  255V

In:  40KA 

Iimp: 20KA

Imax: 80KA

If:  100A

TOV: 300A


Specification of  H2R20-600

Dc spark-over voltage (100V/s)      1)

600V ±20%

Front of wave spark-over voltage at 1.2/50us, 6KV

1500V

Breakdown time   

           - typical values

100ns

20ns

Insulation resistance @DC250V

  10000MΩ

Class I  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μs                               In

Impulse current 10/350μs                                              Iimp

Follow Current at 50/60Hz at 255V                                If

 

255V

40KA

20KA

100A

Class II  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μs                               In

Maximum discharge current 8/20μs                            Imax

Follow Current at 50/60Hz at 255V                              If

 

255V

40KA

80KA

100A

AC discharge current (TOV at 1200V ,1 operation 50Hz,0.2 s)

300A

capacitance at 1MHz

6pF

Weight

~ 5.2g

UL 1449 Certification

On the UL List


 ul.png

Delivery time

20days

Operation and storage temperature

-40 … +90

Marking, Blue  1) At delivery AQL 0.65 level II Military Standard 105E.

2) In ionized mode

3) DC Sparkover may exceed +/-30% ,but will continue to protect without venting

Test according to ITU-T Rec. K.12

2R600 YY

600 - Nominal voltage

YY - Year of production