Tel:+86-755-27465585
Fax:+86-755-27270662
Email:sales@huaandz.com
Website:www.huaandz.com
Add:5F,Building C,No.30,Aviation Road,SanWei,XiXiang Street,BaoAn District,ShenZhen,China
Your Current Location >Home > Products > Gas Discharge Tubes > Φ12x6.5mm - H2R12-1000VE
Φ12x6.5mm - H2R12-1000VE

Φ12x6.5mm - H2R12-1000VE

AC Power line N-PE applications

Class I and Class II Surge protection

Voltage : 1000V

Up: <2000V

Uc:  275V

In:  20KA 

Iimp: 8KA

Imax: 40KA


Specification of  H2R12-1000VE

Dc spark-over voltage (100V/s)      1)

1000V ±20%

Maximum impulse spark-over voltage (1KV/μs)

2000V

Breakdown time   

           - typical values

100ns

20ns

Insulation resistance @DC250V

  1000MΩ

Class I  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μ                              In

Impulse current 10/350μ                                            Iimp

 

275V

20KA

8KA

Class II  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μ                              In

Maximum discharge current 8/20μ                           Imax

 

275V

20KA

40KA

capacitance at 1MHz

5pF

Weight

4g

UL 1449 Certification

On the UL List


 ul.png

Delivery time

20days

Operation and storage temperature

-40 … +90

Marking, Blue

1) At delivery AQL 0.65 level II Military Standard 105E.

    Approvals/ Standards   IEC61643-11

2R1000

YY

1000 - Nominal voltage

YY - Year of production