Tel:+86-755-27465585
Fax:+86-755-27270662
Email:sales@huaandz.com
Website:www.huaandz.com
Add:5F,Building C,No.30,Aviation Road,SanWei,XiXiang Street,BaoAn District,ShenZhen,China
Your Current Location >Home > Products > Gas Discharge Tubes > Φ11.8x17.2mm - H2R12-600xx
Φ11.8x17.2mm - H2R12-600xx

Φ11.8x17.2mm - H2R12-600xx

AC Power line N-PE applications

Class I and Class II Surge protection

Voltage : 600V

Up: <1500V

Uc:  260V

In:  20KA 

Iimp: 8KA

Imax: 40KA

If:  100A

TOV: 300A


Specification of  H2R12-600xx

Dc spark-over voltage (100V/s)      1)

>500V

Front of wave spark-over voltage at 1.2/50us, 6KV

1500V

Breakdown time   

           - typical values

100ns

20ns

Insulation resistance @DC250V

  10000MΩ

Class I  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μ                              In

Impulse current 10/350μ                                             Iimp

Follow Current at 50/60Hz at 255V                                If

 

260V

20KA

8KA

100A

Class II  according to IEC 61643-11

Max continuous operating voltage at 50/60 Hz           Uc

Nominal discharge current 8/20μ                               In

Maximum discharge current 8/20μ                             Imax

Follow Current at 50/60Hz at 255V                                 If

 

260V

20KA

40KA

100A

AC discharge current (TOV at 1200V ,1 operation 50Hz,0.2 s)

300A

capacitance at 1MHz

5pF

Weight

8g

UL 1449 Certification

On the UL List


 ul.png

Delivery time

20days

Operation and storage temperature

-40 … +90

Marking, Blue

1After  the test, DC sparkover  420V

 Approvals/ Standards   EN61643-311   ITU-T Rec. K.12

2R 600 YY

600 - Nominal voltage

YY - Year of production