AC Power line N-PE applications
Class I and Class II Surge protection
Voltage : 800V
Up: <1500V
Uc: 260V
In: 100KA
Iimp: 50KA
Imax: 150KA
| Specification of H2R25-800x | ||
| Dc spark-over voltage (100V/s) 1) | >600V | |
| Front of wave spark-over voltage at 1.2/50us, 6KV | <1500V | |
| Breakdown time - typical values | <100ns <20ns | |
| Insulation resistance @DC250V | 1000MΩ | |
| Class I according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Impulse current 10/350μs Iimp | 
 260V 100KA 50KA | |
| Class II according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Maximum discharge current 8/20μs Imax | 
 260V 100KA 150KA | |
| capacitance at 1MHz | <8pF | |
| Weight | ~ 55g | |
| UL 1449 Certification | Pending | |
| Delivery time | 20days | |
| Operation and storage temperature | -40℃ … +90℃ | |
| Marking, Blue Approvals/ Standards EN61643-311 ITU-T Rec. K.12 | 2R 600 YY | 600 - Nominal voltage YY - Year of production |