AC Power line N-PE applications
Class I and Class II Surge protection
Voltage : 800V
Up: <1400V
Uc: 264V
In: 20KA
Iimp: 8KA
Imax: 40KA
| Specification of H2R16-800xx | ||
| Dc spark-over voltage (100V/s) 1) | 800V ±20% | |
| Maximum impulse spark-over voltage 1KV/μs | 1400V | |
| Breakdown time - typical values | <100ns <20ns | |
| Insulation resistance @DC250V | 1000MΩ | |
| Class I according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Impulse current 10/350μs Iimp | 
 264V 20KA 8KA | |
| Class II according to IEC 61643-11 Max continuous operating voltage at 50/60 Hz Uc Nominal discharge current 8/20μs In Maximum discharge current 8/20μs Imax | 
 264V 20KA 40KA | |
| capacitance at 1MHz | <5pF | |
| Weight | ~ 5g | |
| UL 1449 Certification On the UL List | 
                     | |
| Delivery time | 20days | |
| Operation and storage temperature | -40℃ … +90℃ | |
| Marking, Blue 1) At delivery AQL 0.65 level II Military Standard 105E. 2) In ionized mode Test according to IEC 61643 11 ITU-T Rec. K.12 | 2R800 YY | 800 - Nominal voltage YY - Year of production |